38 Profibus-DP Protocol
jins85e1 4.fm Interface Description(1101)
5.4.1 Assignment of the Profibus Address
The Profibus address has to be assigned with the hardware configuration tool.
After downloading the configuration to the PLC system, the address of the T-Guard™
Profibus Client can be chosen like shown above.
5.4.2 Diagnosis with the T-Guard™ Info Menu
The current state of the T-Guard™ Profibus client is to be seen in the menu:
„Menu - Info - Internal data (Page 8, Info Fieldbus)“
The „State“ has the value „Process_Active (4)“, if the communication has been
established.
The „Device Address“ shows the current Profibus address of the T-Guard™ client.